Whitman Controls

Continuous Level Transmitters

L95 Series Hydrostatic Pressure-Level Transmitter

PRODUCT ID: L95

The L95 Series Level Transmitters leverage high performance silicon piezoresistive pressure sensors as the lead sensing element. The transmitter measures the vertical depth of a column of liquid and converts this depth into standard amplified analog signals.

The L95 Series are IP68-rated devices, featuring a fullysealed structure and made from 304 stainless steel. The cable used in these transmitters is anti-oil, waterproof, and electromagnetic effect-shielded.

This device has a fully integrated structure with sensing element and signal conditioning circuit located and sealed in the probe housing. In application, the transmitter is submerged in the measured liquid with no external adjustment or calibration needed.

  • High Performance silicon piezoresistive sensor
  • Durable 304 stainless steel construction
  • Accurate readings in pressure ranges from 0 – 200m H20
  • IP68 Rated

Overview:

The L95 Series Level Transmitters leverage high performance silicon piezoresistive pressure sensors as the lead sensing element. The transmitter measures the vertical depth of a column of liquid and converts this depth into standard amplified analog signals.

The L95 Series are IP68-rated devices, featuring a fullysealed structure and made from 304 stainless steel. The cable used in these transmitters is anti-oil, waterproof, and electromagnetic effect-shielded.

This device has a fully integrated structure with sensing element and signal conditioning circuit located and sealed in the probe housing. In application, the transmitter is submerged in the measured liquid with no external adjustment or calibration needed.

Key Features:

  • High Performance silicon piezoresistive sensor
  • Durable 304 stainless steel construction
  • Accurate readings in pressure ranges from 0 – 200m H20
  • IP68 Rated

Performance Specifications:

General:

  • Pressure Range: 0.5 – 200 mH20
  • Overpressure: 1.5xFS
  • Accuracy (%FSO):  Min 0.1, Typical 0.25, Max 0.5
  • Temp Coeff – Zero (%FSO): Typical +/- 0.75, Max +/- 1.5
  • Temp Coeff – Span (%FSO): Typical +/- 0.75, Max +/- 1.5
  • Long-Term Stability (%FSO/year): Typical +/- 0.2, Max +/- 0.3

Environmental:

  • Operating Temp. Range: 0 to +70ºC
  • Compensated Temp. Range: 0 to +60ºC
  • Storage Temp. Range: -40 to +125ºC
  • Vibration: 10g(20 to 2000Hz)
  • Shock: 100g(10ms)
  • Cycles: 10x106cycles

Electrical:

  • Output Signal: 4 – 20mA
  • Power Supply(Vs): 12 – 36Vdc
  • Load Resistance: <(Vs-12)/0.02A
  • Insulation Resistance: 100MΩ@50Vdc

Physical:

  • Housing: 304 stainless steel
  • Diaphragm: 316L stainless steel
  • Seal Ring: Viton or NBR
  • Oil Filling: Silicone Oil
  • Protection: IP68

L95 Series Hydrostatic Pressure-Level Transmitter Data Sheet

Technical Information

Switch Selection Guides